Datacenter Plenum Indoor (8B)

Description
Nexans' revolutionary Datacenter Plenum cables with 1.9 mm micro buffer tubes are designed to be used in high density plenum rated environments. Datacenter Plenum is rated for plenum installations and has no gel filler.
Description
Standards
International : EN 50173; ISO/IEC 11801National : ANSI/ICEA S-83-596; ANSI/TIA-568.3-D; NFPA 130; Telcordia GR-409
Description
Nexans' loose tube cable design can be used in all typical campus indoor installations, and is available with standard multimode, single-mode and GIGAlite™ fibers. Datacenter Plenum 8B cable is available in 1 to 192 count fiber constructions. These cables have been thoroughly tested in accordance with Telcordia GR-409 Issue 2, and ICEA-596 Edition 3, where applicable.
These cables are compliant with the Wire and Cable Requirements of NFPA 130 (2014), section 12.2 Flame Spread and Smoke Release. They are suitable for railway and mass transit infrastructure in tunnels, as well as for Tray installations in industrial environments.
Buffer Tube Construction
Dry color coded loose tubes containing up to 8, 250 µm, individually colored fibers.
Applications
Nexans' Datacenter Plenum Loose Tube fiber optic cable is intended for all high speed data applications, including:
- ETHERNET: 10BASE – 400GBASE (10BASE, 100BASE, 1000BASE, 10GBASE, 40GBASE, 100GBASE, 400GBASE)
- Fibre Channel: 1G-FC – 128GFC (1, 2, 4, 8, 16, 32, 128 GFC)
- SONET: OC-1 – OC-768 (OC -1, 3, 12, 24, 48, 192, 768)
- SDH: STM-0 – STM-256 (STM-0, 1, 4, 16, 64, 256)
- OTN: OTU-1 – OTU4 (OTU1, 2, 2e, 2f, 3, 3e2, 4)
- CPRI: CPRI-1 – CPRI-9 (CPRI-1, 2, 3, 4, 5, 6, 7, 7a, 8, 9)
- PON (SMF ONLY): RFoG, APON, BPON, EPON, GPON, WDM-PON, NG-PON
Features
- 1.9 mm space saving buffer tubes housing fibers and aramid strength yarns
- Designed to support Gigabit Ethernet, Gigabit ATM, Fibre Channel and other high-speed applications
- Plenum rating enables installation to go directly through plenum spaces
- All dielectric design
Benefits
-
Compact, plenum rated, flexible loose tube design of all dielectric construction allows for installation in any interior space
-
Optimized access ease with simple, off-the-shelf tools
- No cleaning of gels required for installation, greatly reducing installation time and cost
- System grounding requirements are eliminated
Characteristics
Construction characteristics | |
---|---|
Type of cable | Loose tube |
Jacket Material | Plenum |
Usage characteristics | |
Recommended operating temperature range | 0 .. 75°C |
Ambient installation temperature, range | 0 .. 60°C |
Recommended storage temperature range | -40 .. 75°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Standard Sheath Colors - Nexans Loose Tube
Fiber Type |
Core |
ISO |
Effective Modal |
Overfilled Launch |
Attenuation |
Attenuation |
Attenuation |
Sheath Color |
4 |
8.3 |
OS2 |
NS |
NS |
NS |
0.3 dB/km |
0.2 dB/km |
Yellow |
4 |
8.3 |
OS2 |
NS |
NS |
NS |
0.4 dB/km |
0.3 dB/km |
Yellow |
1 |
62.5 |
OM1 |
200 MHz-km |
200 MHz-km |
3.5 dB/km |
1.0 dB/km |
NS |
Orange |
2 |
50 |
OM2+ |
950 MHz-km |
700 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Orange |
5 |
50 |
OM3 |
2000 MHz-km |
1500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Aqua |
7 |
50 |
OM4 |
4700 MHz-km |
3500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Aqua |
8 |
50 |
OM4+ |
4900 MHz-km |
3675 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Violet |
9 |
50 |
OM5 |
4700 MHz-km |
3500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Lime Green |
NS = Not Specified |