Description
Standards
International : EN 50173; ISO/IEC 11801National : ANSI/ICEA S-104-696; ANSI/ICEA S-83-596; ANSI/TIA-568.3-D; NFPA 130; Telcordia GR-409
Description
Construction
LSZH loose tube cable constructions (up to 288 optical fibers) with aluminum interlock armor and an overall LSZH riser rated jacket. Steel interlock is available.
Features
- These cables are compliant with the Wire and Cable Requirements of NFPA 130 (2014), section 12.2 Flame Spread and Smoke Release.
- Low Smoke Zero Halogen polymer used for jackets and loose tubes.
- Jacketed armor that remains flexible due to the spiral wrap armoring process
- The armored design allows for an easy one-pull installation into any environment
- Sunlight resistant outer jacket per UL 444 clause 7.22 protects the cable in outside plant installations
- Aluminum or steel interlock armor is available
- Aluminum interlock offers 10 to 13 times the impact resistance over all-dielectric optical cable
- Compact outside diameters when compared to plenum innerduct or conduit
Benefits
- Eliminate the need for conduit or plenum innerduct by installing interlock armor cable, providing a significant cost savings in both materials and labor
- Installation time can be reduced by as much as 60% versus installing conduit or innerduct
- Armor-Tek optical fibers cables accommodate last minute relocations or pathway changes whereas innerduct or conduit is not a flexible alternative
- Armor-Tek cables are not governed by fill ratios because they are UL listed as cable assemblies, allowing higher concentrations of cables in an area than allowed with conduit
- Can be installed in campus environments when used with indoor/outdoor rated cables such as Adventum
- Provides additional protection and security for your fiber backbone due to the ruggedness of the armoring materials
Characteristics
Construction characteristics | |
---|---|
Fiber optic type | OM3 50/125 |
Type of cable | Loose tube |
Jacket Material | LSZH-FR |
Sheath colour | Black |
Armour type | Aluminum Interlock |
Dimensional characteristics | |
Tube diameter | 3mm |
Number of optical fibres | 12 |
Cable diameter (Nominal) | 0.618in |
Nominal outer diameter | 15.7mm |
Nominal cable weight | 128lb/kft |
Approximate weight | 191kg/km |
Transmission characteristics | |
Optical performance | EB (50/125 GIGAlite-10, OM3) |
Attenuation, max. 850 nm (cabled) | 3.0dB/km |
Attenuation, max. 1300 nm (cabled) | 1.0dB/km |
Mechanical characteristics | |
Maximum installation tension | 300lb |
Maximum installation tension | 1335N |
Max. Load. Long Term (lbs) | 90.0lb |
Max. Load. Long Term | 400.0N |
Impacts per TIA/EIA FOTP-25 | 2 at 8.83 N-m |
Crush resistance per TIA/EIA FOTP-41 | 440N/cm |
Cable flexibility per TIA/EIA FOTP-104 | 100 cycles |
Usage characteristics | |
Minimum Bending Radius - Install | 9.3in |
Minimum Bend Radius - Install | 23.5cm |
Minimum Bending Radius - LongTerm | 6.2in |
Minimum Bending Radius - LongTerm | 15.7cm |
RoHS compliant | Yes |
Recommended operating temperature range | -40 .. 75°C |
Ambient installation temperature, range | -20 .. 60°C |
Recommended storage temperature range | -60 .. 85°C |
Field of application | Indoor, Outdoor |
Docs and info
Standard Sheath Colors - Nexans Loose Tube - Black
Fiber Type |
Core |
ISO |
Effective Modal |
Overfilled Launch |
Attenuation |
Attenuation |
Attenuation |
Sheath Color |
4 |
8.3 |
OS2 |
NS |
NS |
NS |
0.3 dB/km |
0.2 dB/km |
Black |
4 |
8.3 |
OS2 |
NS |
NS |
NS |
0.4 dB/km |
0.3 dB/km |
Black |
1 |
62.5 |
OM1 |
200 MHz-km |
200 MHz-km |
3.5 dB/km |
1.0 dB/km |
NS |
Black |
5 |
50 |
OM3 |
2000 MHz-km |
1500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
7 |
50 |
OM4 |
4700 MHz-km |
3500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
8 |
50 |
OM4+ |
4900 MHz-km |
3675 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
9 |
50 |
OM5 |
4700 MHz-km |
3500 MHz-km |
3.0 dB/km |
1.0 dB/km |
NS |
Black |
NS = Not Specified |
-
Optical Fiber Cable Applications
Nexans' fiber optic cable is intended for all high speed data applications, including:
- ETHERNET: 10BASE – 400GBASE (10BASE, 100BASE, 1000BASE, 10GBASE, 40GBASE, 100GBASE, 400GBASE)
- Fibre Channel: 1G-FC – 128GFC (1, 2, 4, 8, 16, 32, 128 GFC)
- SONET: OC-1 – OC-768 (OC -1, 3, 12, 24, 48, 192, 768)
- SDH: STM-0 – STM-256 (STM-0, 1, 4, 16, 64, 256)
- OTN: OTU-1 – OTU4 (OTU1, 2, 2e, 2f, 3, 3e2, 4)
- CPRI: CPRI-1 – CPRI-9 (CPRI-1, 2, 3, 4, 5, 6, 7, 7a, 8, 9)
- PON (SMF only): RFoG, APON, BPON, EPON, GPON, WDM-PON, NG-PON
-
Cross-section Diagram - N19_.LTK0012-_Z
-
Manufacturing Release - Nexans
IMPORTANT NOTICE: This product specification is provided for informational purposes only in order to illustrate typical product constructions, applications and/or methods of installation. Because conditions of actual installation and use are unique and will vary, Nexans makes no representation or warranty as to the reliability, accuracy or completeness of this data, even if Nexans is aware of the product's intended use or purpose. Furthermore, this data does not constitute, nor should it be regarded or relied upon, as professional engineering advice. Installation of product should only be done by qualified personnel and in conformance with all safety, electrical and other applicable codes, standards, rules or regulations. Appropriate and correct product selection, installation and use, and compliance with all such codes, standards, rules and regulations, is a customer/end-user responsibility. Product specifications, standards, programs or services are subject to improvement or changes without notice. Nexans accepts no liability for typographical errors, technical inaccuracies, omissions or misuse of the information contained herein. Changes will be periodically made to address any such issues.